Skip to content

Home, HVAC & Safety Mesh · ISO 16852 / API 2000

ISO 16852 Crimped Ribbon Flame Arrester Element Specifications

A circular crimped ribbon stainless steel flame arrester element showing spiral wound corrugated metal channels

Crimped Ribbon Flame Arrester Element is used for stopping flame propagation in vent and process lines by quenching it in narrow channels formed between spiral-wound crimped and flat metal ribbons. ISO 16852 is the reference cited for it on drawings, datasheets and purchase orders.

What ISO 16852 Means for Crimped Ribbon Flame Arrester Element

The dimensions in the table below are supplied to suit ISO 16852. Where the standard sets requirements for the finished appliance, device or system, compliance testing of that assembly stays with its manufacturer; we supply the metal mesh part to the drawing and can provide material certificates and dimensional reports with the shipment.

Crimped Ribbon Flame Arrester Element Dimensions

SizeOuter diameter (mm)Element thickness (mm)Crimp height (mm)Gas groupMaterial
DN 2560250.5IIASS316L
DN 50100300.5IIA / IIB3SS316L
DN 100180400.4IIB3SS316L
DN 150250500.3IICSS316L

Specifying Crimped Ribbon Flame Arrester Element Beyond the Standard

  • Gas group: Choose crimp height for IIA, IIB or IIC gases — smaller gaps for more reactive gases.
  • Element depth: Deeper elements for longer burn and detonation duties.
  • Certification: Must match the tested housing per ISO 16852.

When Crimped Ribbon Flame Arrester Element Is Not the Right Choice

Not a pressure-vacuum relief valve.

Technical Drawing

Customize the parameters below — every spec field is editable, and the drawing redraws to match the values you choose. Changing the size will snap the other fields to that size's standard values; you can then override any individual value.

Sends the selected values to the quote form below.

Request a Quote

Adjust the parameters in the drawing above and click "Request this configuration" to send the exact specification straight to this form.

Request a Quotation

Specification
Business Information

Dimensions & Specifications (ISO 16852 / API 2000)

SizeOuter diameter (mm)Element thickness (mm)Crimp height (mm)Gas groupMaterial
DN 2560250.5IIASS316L
DN 50100300.5IIA / IIB3SS316L
DN 100180400.4IIB3SS316L
DN 150250500.3IICSS316L

Frequently Asked Questions

Can flame arrester elements be cleaned?

Yes, by solvent or ultrasonic cleaning, then inspection.

How does a crimped ribbon flame arrester work?

Narrow channels absorb heat and quench the flame front.

How do I request a quotation?

Use the technical drawing on this page to pick the exact specification, then submit it with the quote form. We respond within one business day.